Cooling tower fill PVC plastic thin sheets pack Latest material cooling tower infill provider
PVC Filler for Cooling Tower
(1) Weight: 18Kgs/Cubic Meter
(2) Material: PP,PVC,FRP
(3) Thickness: 0.25-0.65mm
PVC Filler for Cooling Tower
Cooling Tower Fill is one of the most important components for exchange of gas and water in cooling Tower.It is the major parts to improve the efficiency of cooling tower and make sure the economy and safe operation. With the development of the plastic industry, counter-current tower drench water plastic packing "S" shape ladder wave, obliquely wave, which has the heat dissipation ,good performance ,Ventilated small resistance, durable, based on the easy and other advantages, it is widely used in different types of large, medium, small, cooling tower.
Cooling Tower Fills(Black,White,Blue)
Media and type:
|
Length(mm) |
Height(mm) |
Film thickness(mm) |
|||
Size |
Tolerance |
Size |
Tolerance |
Size |
Tolerance |
|
"S" Wave |
1000 |
±10 |
500 250 |
±5 |
0.4 |
±0.05 |
2000 |
±10 |
500 250 |
±5 |
0.4 |
±0.05 |
|
Double Inclined |
1000 |
±10 |
500 250 |
±5 |
0.4 |
±0.05 |
Inclined Wave |
1000 |
±10 |
500 |
±5 |
0.4 |
±0.05 |
Cooling Tower Fills(Black,White,Blue)
Heating Power and Resistance Character:
|
Fill Height |
Cooling No. (Volume Scattered Coefficient: Ka) |
Resistance Equotion:P/p1=9.81*A*Vcpm A.M expression |
"S" Wave |
1m |
=1.83y0.65 |
A=-0.0019q2+0.0685q+0.06543 |
Ka=4746g0.56q0.36 |
M=-0.0028q2-0.0170q+1.9480 |
||
Double Inclined |
1m |
=1.92y0.68 |
A=-0.0006q2+0.0306q+0.06376 |
Ka=4342g0.69q0.36 |
M=-0.0002q2-0.0026q+1.9029 |
||
Inclined Wave |
1m |
=1.85y0.64 |
A=-0.0001q2+0.189q+0.6374 |
Ka=4296g0.63q0.38 |
M=-0.0006q2-0.0122q+2.0178 |
Remark: P-Fill Resistance,Pa P1=Air density,kg/m3 q---Spray waterdensity,t/(m2*h) Vcp-Spray Fill Average Wind Speed m/s
g--Ventilation density kg/(m2*h g-gas water radio